Analisis Susut Energi Pada Titik Sambung Ring Penyulang Sepat Menggunakan Thermovision Di PT PLN (Persero) Rayon Kota Metro

Daswaeptia Dj, JECKSON JECKSON, Arif Fauzan Serio Lago

Abstract


In electric energy dispatch process, interference were often found especially at medium voltage network. One of major problem from this processis the loss of electricsl energy which called losses. Losses caused be technical and non technical factors.One causes of the factor itself come from poor connecting point. This paper presents losses calculating with the result which caused by poot connecting point. Power loss count by long and cross sectional area at the connecting point. It also infected by the amount of load current flowing at that point. The biggest value of power loss occur at the connecting point which use joint sleeve. Otherwise, the smallest value of power loss occur at the connecting point which use compression connector (CCO).

Keywords


power loss, medium voltage, connecting point, distribution,thermovision